Adjustment Factors for More Than 3 Current Carrying Conductors
Number of Conductors in a Raceway |
Percent of Total Value |
4 – 6 |
80 |
7 – 9 |
70 |
10 – 20 |
50 |
21 – 30 |
45 |
31 – 40 |
40 |
41 or Above |
35 |
Table 310.15(C)(1), 2020 NEC®
Warning: For safety, call a licensed electrician or consult the NEC®. All licensed electricians have passed examinations covering the
National Electric Code®, know state and local building codes, and may carry insurance to cover damages.