Item Comparison: ECNR60, TR60R

Item

ECNR60 - 60A 250V Class RK5 Time Delay CL Fuse - Edison

ECNR60
60A 250V Class RK5 Time Delay CL Fuse

$19.78 Each

$197.80 (10 Each)

QTY:
Each
Add
TR60R - 250V RK5 TD Fuse - Mersen

TR60R
250V RK5 TD Fuse

$14.55 Each

$14.55 (1 Each)

QTY:
Each
Add
Nacogdoches 25 0
All Stores 3,898 11
Vendor Edison Mersen
Catalog Number ECNR60 TR60R
Manufacturer Number ECNR60 TR60R
Category Distribution Fuses - Dual Element Distribution Fuses - Current Limiting
Classification Fuses & Fuse Accessories Current Limiting Fuses
UNSPSC 39121604 - Time delay fuses 39121604 - Time delay fuses
UPC/EAN/GTIN 00782634507390 00782001747947
Weight per package 0.12 (lbs/each) 0.135 (lbs/each)
Description ECNR60 60A 250V Class RK5 Time Delay CL Fuse
Ul Class RK-5 Time Delay
TR60R 250V RK5 TD Fuse
Fuse TR-R - Class RK5 - Time-Delay 250VAC 250VDC 60A Ferrule Tri-Onic®
Minimum Order QTY 1 Unit 1 Unit
Unit/Foot $19.78 (Each) $14.55 (Each)
Carton/Reel $19.78 (1 Each) $14.55 (1 Each)
Standard Packaging/Reel $197.80 (10 Each) $14.55 (1 Each)
amperage rating - 60
Characteristics Dual Element, 10 Second Time Delay -
connection - Ferrule
Current Rating 60 Amp -
interrupt rating 200000 A 200
Interrupting Rating 200000 Amp (DC) -
Terminal Type Ferrule -
Voltage Rating 250 Volt AC/125 Volt DC 250
Body Material - PolyTube
Diameter 0.81 INCH -
Length 3 INCH -
Overall Length 3 in -
Size - 3 x 0.81
Additional Information Application General-Purpose Including Lighting, Heating and Other Non-Inductive Load -
Commodity Description DUAL ELEMENT FUSES -
Description 60A 250V CLASS RK5 TIME DELAY CL FUSE 250V RK5 TD FUSE
extra long description CLASS RK5 TYPE; 3 INCH; UL 248-12, CE, CSA C22.2 APPROVAL; 250 VOLT AC/125 VOLT DC VOLTAGE RATING; 0.81 INCH DIAMETER; 200000 AMP (DC) INTERRUPTING RATING; 60 AMP CURRENT RATING; FERRULE TERMINAL TYPE; DUAL ELEMENT, 10 SECOND TIME DELAY CHARACTERISTICS; EDISON BRAND; APPLICATION GENERAL-PURPOSE INCLUDING LIGHTING, HEATING AND OTHER NON-INDUCTIVE LOAD; ECNR MODEL Mersen TR60R Fuse TR-R - Class RK5
Features These fuses are recommended for AC power distribution system mains, feeders and branch circuits having inductive loads (motors, transformers) or non-inductive loads (lighting, heating) where the available short-circuit current does not exceed 200,000 RMS symmetrical amps. These “dual-element, time-delay” fuses have minimum industry standard time-delay of 10 seconds at 5 times the fuse rating (8 sec. minimum for 250V, 30A and less). The time-delay characteristics of these fuses typically allows them to be s Tri-Onic TR-R current-limiting time-delay fuses are engineered for overcurrent protection of motors, transformers, service entrance equipment, feeders and branch-circuits. The time-delay characteristics of the TR-R safely handle harmless starting currents and inrush currents associated with today's motors and transformers.
Long Description UL CLASS RK-5 TIME DELAY Fuse TR-R - Class RK5 - Time-Delay 250VAC 250VDC 60A Ferrule Tri-Onic®
Product Type Time Delay Power Fuse Fuse TR-R - Class RK5 - Time-Delay 250VAC 250VDC 60A Ferrule
Short Description Power Fuse, 60 A, 250 VAC/125 V dc, Time Delay, RK5 Class, ID 250V 60A 3x13/16 RK5 TD F
Special Features - Time-delay Current-limiting AC & DC rated Optional solid state SmartSpot blown fuse indicator Time-delay for motor start-ups and transformer inrush currents without nuisance opening Current-limiting for low peak let-thru current Rejection-style design prevents replacement errors (when used with recommended fuse blocks) Easy-to-read label for quick brand recognition and replacement Metal-embossed date and catalog number for traceability and lasting identification Fiberglass body provides dimensional stabili
AC Voltage Rating - 250
class - RK-5
Connection Type Ferrule End x Ferrule End -
Fuse Class RK5 Class -
Fuse Type Ferrule -
package quantity 10 CT -
Response Time 10 s @ 500% -
Standards Met UL Listed Std. 248-12,Class RK-5, Guide JDDZ, File E162363;CSA Certified C22.2 No. 248.12, Class 1422-02, File 700489;CE Certified -
Made in USA yes -
Brand EDISON FUSE, INC. Ferraz Shawmut
Manufacturers Part Number ECNR60 TR60R
Model ECNR -
sub brand - Tri-Onic®
Category Description Fuses & Fuse Accessories -
Type CLASS RK5 CLASS RK5
Weight 1 lb;0.45 kg -
Application AC Power Distribution System mains, Feeders, and Branch Circuit;Protection of Motor and Motor Branch Circuit;Protection of Transformer and inductive Load;All General Purpose Application including Lighting, Heating and Other Non-inductive Load Motor circuits Mains Feeders Branch circuits Transformers Service entrance equipment General-purpose equipment
Approval UL 248-12, CE, CSA C22.2 -
Mounting - Clip
standard - UL listed to standard 248-12 File E2137 CSA certified to standard C22.2 no. 248.12 DC listed to UL standard 248 TRS only
 